Content contact: Engr. Muhammad Aalam · Sources, corrections & editorial standards
Industrial Applications & Working Principles
Chillers cool process water, moulds, reactors and air-conditioning coils. Match the supply-temperature requirement to the process and fluid. Water and glycol mixtures have different density, heat capacity and freezing behaviour, so water-only calculations must not be applied blindly to a brine circuit.
In vapour-compression refrigeration, refrigerant absorbs heat while evaporating at low pressure. The compressor raises the vapour pressure, the condenser rejects heat, and the expansion device reduces pressure before the evaporator. The condenser rejects the cooling load plus compressor work; compressor electricity is not the cooling duty.
Water-cooled chillers depend on condenser-water flow and heat rejection by a tower. Air-cooled chillers depend on coil condition and entering-air conditions. A change in condensing pressure may originate outside the refrigerant circuit. Compare water or air conditions before concluding that the refrigerant charge is wrong.
Controls regulate capacity while maintaining protection against freezing, excessive pressure, lubrication faults and unsafe starts. Flooded and direct-expansion evaporators use different refrigerant arrangements. Superheat, subcooling and approach targets must come from the installed model—not a universal table.
System Flow & Operating Sequence
Establish the approved fluid flow and readiness permissives → start through the manufacturer controller → regulate load → reject heat through the condenser circuit → unload and stop through the approved sequence. This is a process description, not a manual restart procedure after a protective trip.
Engineering Formula & Variable Definitions
Q = ρ × V̇ / 3,600 × cp × (Tr − Ts); COP = Q / P; TR = Q / 3.51685284
| Symbol | Meaning and units |
|---|---|
| Q | Cooling duty, kW thermal |
| ρ | Fluid density, kg/m³ |
| V̇ | Fluid volume flow, m³/h |
| cp | Specific heat, kJ/(kg·K) |
| Tr, Ts | Return and supply temperatures, °C |
| P | Measured electrical input at the stated boundary, kW |
| TR | Refrigeration tons; 1 TR = 3.51685284 kW thermal |
Step-by-Step Numerical Example
Illustrative assumptions only—not plant results, specifications or approved operating targets.
- Assume clean water: ρ = 997 kg/m³, cp = 4.186 kJ/(kg·K), flow = 120 m³/h, return = 12°C, supply = 7°C.
- Mass flow = 997 × 120 / 3,600 ≈ 33.233 kg/s; retain unrounded values in subsequent calculations.
- Duty = (997 × 120 / 3,600) × 4.186 × 5 ≈ 695.574 kW; capacity ≈ 197.783 TR.
- At 120 kW chiller input, COP ≈ 5.796 and input per ton ≈ 0.607 kW/TR.
What the Result Means
These assumed values demonstrate the calculator’s water-only model. They are not a guaranteed efficiency or pass/fail criterion. Whole-plant COP must also include the chosen pump, tower and auxiliary boundary. Use actual fluid properties for glycol.
Operating Baseline & Equipment-Specific Limits
Record healthy performance at comparable load, supply temperature and condenser conditions. Flow envelope, freeze-protection settings, permitted starts, refrigerant limits and approach expectations are model-specific. A historical temperature difference must be interpreted with flow and load.
Required Measurements & Instruments
Collect paired entering/leaving fluid temperatures, calibrated flow, electrical input, condenser conditions and alarm history. Temperature sensors should be compared as a pair because error in a small temperature difference can dominate the cooling-duty estimate.
Energy Efficiency & Optimisation
Investigate low temperature difference, unnecessary pumping and deteriorating heat transfer as a system. Compare total plant power at equal useful cooling. Setpoint and sequencing changes require process approval and checks of minimum flow, freeze protection and compressor operating limits.
Safety & Environmental Considerations
Refrigerant work requires authorised personnel and approved recovery practices. Do not vent refrigerant or prescribe a top-up from one pressure reading. Control condenser-water chemistry, leakage and treatment disposal under site requirements.
Technical Reading & References
These sources provide background. Use the installed manual and locally adopted standard for actual work. A linked standard does not certify this page or your installation; independent technical review has not been claimed.
